DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
12. Installer settings
KT.TEL: setting OPEN CLOSE OPEN CLOSE
I.TEL: status OPEN CLOSE CLOSE OPEN
I.TEL: ANTIFR Boiler
operating
mode selected
Antifreeze
mode
Antifreeze mode Boiler operating mode
selected
DHW+HEAT Hot water storage
tank affected to
heating and
domestic hot
water
Burner, heating load pump
(auxiliary pump) and DHW load
pump shut down.
Boiler operating mode selected.
HEAT Hot water storage
tank affected to
heating only
Heating load pump (auxiliary
pump) shut down.
Burner shut down if domestic hot
water requirement.
DHW Hot water tank
affected to
domestic hot
water only
The DHW function is not
ensured by the boiler.
THERM A Connection of a
room thermostat
to circuit A
Circuit A in Antifreeze mode.
SWIM. Used for the
remote control of
pool reheating
shutdown
Pool heating off.